Wiring: Safety Relay to Servo Module Fault Input

From ATTWiki
Jump to: navigation, search

Contents

About the Wiring Standard

For increased safety, newer SMT benders are wired so that the servo modules fault inputs receive signal from the safety relay. The fault input points on the I2T servo modules are at points 8 and 10 on the bottom row of the terminal strips on these modules.

How to Determine Which Wiring Setup a Bender Uses

Warning.jpg

Gear warning.jpg WARNING!

Only experienced electrical technicians should perform what we describe next.

There can be high voltages and currents of electricity flowing through the electrical panel.

You can determine if the wiring on your bender is older by examining these points. If the points have wires labeled "2451", then your bender uses the older style of wire routing. To re-route the wiring to be compatible with newer benders, remove the 2451 wires from these points, then replace them with wires from the top row terminal strip point 16 of either module 192.168.0.201 or module 192.68.0.205.

Cncbender powerwire toservofaults.jpg

I2T HMI Fault Masking

For this wire change to work properly, it is also important to ensure that the faults are not masked in the I2T setup.


Tools/Parts Needed

14 Gauge THHN stranded wire

14awg thhn wire.jpg

Vinyl Insulate Terminal Pin for 14 gauge wire (See 159-1617 Kobiconn Terminals Pin Blue 16-14 at Mouser.com)

Pinterminal.jpg

Jumper bar (Automationdirect.com DINnectors DN-82J10)

Jumperbar dn-82J10.jpg

Crimper for terminal pins, screw drivers, diagonal cutters for cutting the jumper bar

Screwdrivers.jpg